Product Information
The Seaward PV150 Solar Installation Tester allows electrical safety and performance verification of photovoltaic installations in a safe and easy-to-use device.
> Save time using a number of different measuring tools in the field with this fast and comprehensive solar PV tester.
> The PV150 features a safe test connection meaning you can safely test energised arrays.
> The unit can also wirelessly capture and record real time irradiance, ambient temperature and PV module temperature measurements from the Solar Survey 200R.
> 200 datasets can be stored on the PV150 and downloaded to the SolarCert software so you can create professional reports for your customers.
Open Circuit Voltage Measurement (PV Terminals) | |
Display Range | 0.0VDC – 1000VDC |
Measuring Range | 5.0VDC – 1000VDC |
Resolution | 0.1VDC maximum |
Accuracy | ± (0.5 % + 2 digits) |
Enunciators | DC voltage polarity correct or reversed |
Short Circuit Current Measurement (PV Terminals) | |
Display Range | 0.00ADC – 15.00ADC |
Measuring Range | 0.50ADC – 15.00ADC |
Maximum Power | 10kW |
Resolution | 0.01ADC maximum |
Accuracy | ± (1% + 2 digits) |
Earth Continuity Resistance Measurement (4mm Terminals) | |
Test Voltage Open Circuit | >4VDC, nominal |
Test Current into 2 Ω | >200mA |
Display Range | 0.00Ω – 199Ω |
Measuring Range (EN 61557-4) | 0.05Ω – 199Ω |
Resolution | 0.01Ω maximum |
Accuracy | ± (2% + 5 digits) |
Test Leads Zero | Zero up to 10Ω, by zero button |
Visible Warning | ≥30V AC or DC at inputs |
Circuitry Protection | Test inhibited if ≥30V AC or DC at inputs |
Repeat tests as per IEC61557-4 | Approx 4000 1 second test |
Insulation Resistance (Auto Test Sequence, PV Terminals and Red 4mm Terminal) | |
Test Voltage Open Circuit | 250V, 500V, 1000V (as per IEC61557-2) |
Test Voltage Specification | -0% +20% (open circuit) |
Test Voltage @ 1mA | >1mA into UN x (1000Ω/V) |
Test Current Short Circuit | <2mA |
Display Range | 0.05MΩ – 199MΩ |
Measuring Range (EN 61557-2) | 0.05MΩ – 199MΩ |
Resolution | 0.01MΩ maximum |
Accuracy | 0.05MΩ – 100MΩ ± (5% + 5 digits) |
101MΩ – 199MΩ ± (10% + 5 digits) | |
Visible Warning | ≥ 30V AC or DC at inputs |
Circuitry Protection | Test inhibited if ≥ 30V AC or DC at inputs |
Repeat tests as per IEC61557-4 | Approx 3000 1 second tests |
DC Operating Power (via AC/DC Current Clamp and PV Terminals) | |
Display Range | 0.00kW – 40kW |
Measuring Range | 0.50kW – 40kW |
Resolution | 0.01kW |
Accuracy | ± (5% + 5 digits) |
Operating Current (via AC/DC Current Clamp) | |
Display Range | 0.1A – 40.0A |
Current Measuring Range | 0.1A – 40.0A DC |
0.1A – 40.0A AC 50-60Hz | |
Resolution | 0.1A |
Accuracy | ± (5% + 2 digits) |
Instrument Dimensions and Weight | |
Weight | 0.95kg |
Dimensions | 26.4 x 10.7 x 5.8cm |
Display | Custom LCD with backlight |
Power Source | 6 x 1.5V AA cells |
Battery life | >1000 test sequences |
Auto power down | User-programmable |
Onboard memory | Up to 200 complete test datasets |
Connectivity | |
USB download to PC (CSV format) | |
Wireless “Solarlink TM” to Survey 200R (range ~30m/100ft) | |
Service | 2-year warranty (subject to terms and conditions, available at /warranty) |
Software compatibility | ompatible with SolarCert software (English language only) |