Test Function Specifications
The operational error specification reference for digit counts is defined as ±(% of reading + digit counts). The operational error for other specifications that reference a percentage is defined as the percentage of the reading, unless otherwise specified. The operational error specification reference temperature for all readings is 23 °C ±5K, with a temperature coefficient of 0.1 %/°C.
Test/function |
Display range |
Measurement range |
Operational error |
Nominal values |
PE pre-test |
Touch voltage, safe range |
≤50 V AC/DC |
-50% |
-- |
Touch voltage, dangerous range |
>50 V AC/DC |
+0% |
-- |
Visual inspection |
See checklist |
Earth bond, RLO[1] |
-- |
@ >200 mA Itest |
Insulation, RINS[1] |
-- |
@ 500 V Unom |
Loop/Line impedance[1] |
-- |
no trip loop |
RCD/RDC-DD pre-test |
Uf |
5V to 110V |
-(0 % + 0 digits),
+(10 % + 3 digits) |
@ Itest
0.33 x IΔN AC |
Re |
166 Ω to 3667 Ω |
-10 % to +15 % |
RCD test (IΔN 30 mA) |
RCD type A, B/B+, RDC-PD |
-- |
@ mains 100 V AC to 253 V AC |
RCD trip time with AC, half wave, DC (0°, 180°) |
x0.5 (30 mA) |
0 ms to 510 ms |
±(2 % + 3 ms) |
x1 (30 mA) |
TN: 0 ms to 310 ms
TT @120 V: 0 ms to 310 ms TT @230 V: 0 ms to 210 ms |
x5 (30 mA) |
0 ms to 50 ms |
Ramp current (0°, 180°) |
AC @RCD type B/B+ |
12.0 mA to 36.0 mA, 17 steps with
1.5 mA |
±1.5 mA |
AC half wave @RCD type A and RCD-PD |
7.5 mA to 48.0 mA, 28 steps with
1.5 mA |
DC @RCD type B/B+ |
12.0 mA to 66.0 mA, 37 steps with
1.5 mA |
Test/function |
Display range |
Measurement range |
Operational error |
Nominal values |
RDC-DD test (IΔN +6 mA EV) |
Trip time (0°, 180°) |
@ mains 100 V AC to 253 V AC |
+3 mA DC |
0.000 s to 10.100 s |
±(2 % + 3 ms) |
+6 mA DC |
+60 mA DC |
0 ms to 310 ms |
+200 mA DC |
0 ms to 110 ms |
Ramp current (0°, 180°) |
smooth ramp
2.0 mA to 6.0 mA |
±0.6 mA |
Mains voltage |
L-N, L-PE, N-PE |
0 V to 280 V |
0V to 253 V |
±(3 % + 3 digits) |
RIN L-N:
>30 MΩ, RIN L-PE:
>10 MΩ,
40 Hz to 70 Hz,
crest factor 2, Vmax peak: 560 V |
L-L |
0 V to 490 V |
0 V to 440 V |
RIN L-L: >30 MΩ,
40 Hz to 70 Hz,
crest factor 2, Vmax peak: 980 V |
Frequency |
40.00 Hz to 70.00 Hz |
±0.20 Hz |
-- |
Phase sequence |
right, left, none |
-- |
voltage imbalance:
<20 % voltage difference between phases,
phase imbalance:
120° ±10° |
50 V to 280 V
phase to N |
CP signal analysis |
Voltage |
-15.000 V to
15.000 V |
-15.000 V to
-2.000 V,
2.000 V to
15.000 V |
±0.5 % |
RIN: 1 MΩ
0.9000 kHz to
1.1000 kHz;
UCP+ >2.000 V,
UCP- <-2.000 V |
PWM duty cycle |
2.0 % to 98.0 % |
3.0 % to 97.0 % |
±5 digits |
Current indication |
0.0 A to 80.0 A |
-- |
Based on duty cycle[3] |
Frequency |
0.9000 kHz to 1.1000 kHz |
0.001 |
CP state indication |
A, B, C, D |
-- |
Based on voltage[2] |
x1, x2 |
-- |
Based on frequency[2] |
Test/function |
Display range |
Measurement range |
Operational error |
Nominal values |
CP state simulation |
A |
-- |
>900 kΩ ±0.2 % |
-- |
B |
Upper level: 4610 Ω
±0.2 %[2]
Nominal level: 2740 Ω
±0.2 %[2]
Lower level: 1870 Ω
±0.2 %[2] |
C |
Upper level: 1723 Ω
±0.2 %[2]
Nominal level: 1300 Ω
±0.2 %[2]
Lower level: 909 Ω
±0.2 %[2] |
D |
Upper level: 448 Ω
±0.2 %[2]
Nominal level: 270 Ω
±0.2 %[2]
Lower level: 140 Ω
±0.2 %[2] |
PP state simulation |
open |
-- |
>900 kΩ |
-- |
13 A |
1500 Ω ±1.5 %[2] |
20 A |
680 Ω ±1.5 %[2] |
32 A |
220 Ω ±1.5 %[2] |
63 (70) A |
100 Ω ±1.5 %2] |
Error |
<60 Ω (56 Ω ±5 %) |
Fault simulation |
PE error (earth fault/PE open) |
-- |
-- |
-- |
CP error E @ 0 Ω
or 120 Ω |
-0 Ω/ +2 Ω,
120 Ω ±1.5 %[2] |
Diode short |
-- |
Error D |
PP voltage measurement
(Type 2 with socket) |
0.10 V to 15.00 V |
±(1.0 % + 3 digits) |
RIN: 1 MΩ |
Test/function |
Display range |
Measurement range |
Operational error |
Nominal values |
PP resistor measurement |
Type 2 with cable (Rc) |
50.0 Ω to 499.9 Ω
500 Ω to 5000 Ω |
±1.0 % |
-- |
Type 1 with cable (S3, R6, R7) |
CP resistor measurement (R1) |
800 Ω to 1200 Ω |
±1.0 % |
-- |
[1] The test requires a multifunction tester (MFT). Refer to the MFT documentation for details on the display range, measurement range, and operational error or accuracy values.
[2] In accordance with IEC 61851-1.
[3] In accordance with Table A.8 of IEC 61851-1.
General Specifications |
Input electrical ratings |
1 Φ: 250 V max
3 Φ: 230/400V max, 50/60 Hz, max 1 A |
Internal power consumption |
3 W max |
Size (H x W x D) |
~(263 mm x 123 mm x 63 mm)
~(10.35 in x 4.84 in x 2.48 in), without the TY1 or TY2 plug |
Weight |
~0.9 kg, without the TY1 or TY2 plug
~1.4 kg, with the TY1 or TY2 plug |
Battery |
4 x AA/IEC LR6 alkaline or IEC HR6 NiMH |
Temperature |
Operating |
-10 °C to 40 °C (14 °F to 104 °F) |
Storage |
-20 °C to 50 °C (-4 °F to 122 °F) |
Relative humidity |
Operating |
10 % to 85 %, 0 °C to 40 °C
(32 °F to 104 °F), non-condensing |
Storage |
up to 95 % |
Wireless radio, Bluetooth 5.0 |
Frequency range |
2412 MHz to 2462 MHz |
Output power |
<100 mW |
Altitude |
3000 m |
Safety |
IEC 61010-1: Pollution Degree 2, IEC 61010-2-030, CAT II 300 V, Protection Class II |
Performance |
IEC 61557-1, IEC 61557-6, IEC 61557-7, IEC 61557-10 |
Ingress protection |
IEC 60529: IP40 |
Electromagnetic Compatibility (EMC)
International Standards
- IEC 61326-1: Basic Electromagnetic Environment
- CISPR 11: Group 1, Class A
Group 1: This equipment intentionally generates and/or uses conductively coupled radio frequency energy, which is essential for its internal function.
Class A: This equipment is suitable for use in all establishments except domestic environments and those directly connected to a low-voltage power supply network that serves residential buildings. Due to conducted and radiated disturbances, ensuring electromagnetic compatibility in other environments may be challenging.
⚠️ Caution: This equipment is not intended for use in residential environments and may not provide adequate protection against radio interference in such settings. When connected to a test object, emissions exceeding the levels required by CISPR 11 may occur.
Korea (KCC) – Class A Equipment (Industrial Broadcasting & Communication Equipment)
Class A: This equipment meets the requirements for industrial electromagnetic wave equipment, and the seller or user should take note of this. It is intended for use in business environments and must not be used in homes.