OPTIMIZER3 CIRCUIT BREAKER MONITORS
Model |
Description |
OM3D |
Optimizer3 circuit breaker monitor, density measurement-ready |
OM3D-F |
Optimizer3 circuit breaker monitor, density measurement-ready with fiber-optic communication port |
OM-MMK |
Optimizer3 magnetic mounting kit |
Magnetic Mounting Kit
- Non-drill, easy mounting to ferrous metal panels and enclosures
- NEMA cabinet rating is not compromised by having to drill
- All hardware included: (4) clip nuts, (4) screws, and (4) magnets
CURRENT TRANSFORMER PICKUP COILS
Current transformer pickup coils enable the Optimizer3 to measure real-time current flow in the bushing current transformer secondaries. The split-core design allows the pickup coils to be applied to secondaries of bushing current transformers without disassembling or disconnecting the cabling for fast and convenient installation. They are available in eight current ranges to accommodate all applications.
Model |
Description |
CT-20 |
Current transformer pickup coil, 20 Amps |
CT-30 |
Current transformer pickup coil, 30 Amps |
CT-50 |
Current transformer pickup coil, 50 Amps |
CT-100 |
Current transformer pickup coil, 100 Amps |
CT-160 |
Current transformer pickup coil, 160 Amps |
CT-250 |
Current transformer pickup coil, 250 Amps |
CT-400 |
Current transformer pickup coil, 400 Amps |
CT-800 |
Current transformer pickup coil, 800 Amps |
Specifications
- Current sensors are specifically designed for use with Optimizer CT input circuitry
- Includes 8' wire lead
- Accuracy greater than 1%
SF6 GAS MONITORING
The Optimizer3 aids in the mandatory compliance reporting required by the EPA, resources boards, and other regulatory agencies by monitoring for SF6 gas leaks and related indicators and automatically reporting any fugitive emissions.
SF6 GAS DENSITY SENSOR
Model |
Description |
DSDP |
Digital SF6 gas density sensor, temperature & density, 10 ft cable |
DSDP-20 |
Digital SF6 gas density sensor, temperature & density, 20 ft cable |
DSDP-30 |
Digital SF6 gas density sensor, temperature & density, 30 ft cable |
DSCC |
1/2" NPT conduit fitting adapter |
Specifications
- Density range: 0 to 60 grams per liter (kg/m3) SF6
- Temperature range: -40 to 85 °C
- Mounting thread: Male 3/8" BSPP
- Seal: Neoprene O-Ring
- Accuracy: 1.8% of full scale max.; 1.0% of full scale typ.
- Temperature signal: +/- 1°C at ambient temperature +/- 3°C at -40 to 85 °C
- Output signal: Digital (frequency & pulse-width modulated)
- Supply voltage: 10 to 20 Volts DC
- Electrical connections: 2-wire
- Operating temperature -40 to 70 °C
- Operating pressure -1 to 20 Bar
SF6 GAS PRESSURE SENSOR
The SF6 gas pressure sensor measures the temperature-compensated pressure of SF6 gas. The temperature and the compensated pressure measurements are digitally transmitted over a two-wire, power-line-carrier interface.
Model |
Description |
PSDP |
Digital SF6 gas pressure sensor, temp & pressure, 5 meter cable |
PSDP-10 |
Digital SF6 gas pressure sensor, temp & pressure, 10 meter cable |
OM-SC5 |
5 meter cable with 90 degree connector |
OM-SC10 |
10 meter cable with 90 degree connector |
Specifications
- Pressure range: 0 to 10 Bar Abs at 20 °C compensated
- Temperature range: -40 to 85 °C
- Mounting thread: Male 3/8" BSPP
- Seal: Neoprene O-Ring
- Pressure accuracy: +/- 1% of full scale range at 85 °C +/- 2.2% of full scale range at -40 to 85 °C
- Temperature accuracy: +/- 3°C
- Output signal: Digital (frequency & pulse-width modulated)
- Supply voltage: 15 to 30 Volts DC
- Electrical connections: 2-wire
- Operating temperature -25 to 80 °C
- Operating pressure: 0 to 20 Bar absolute
SF6 GAS DEW POINT TEMPERATURE SENSOR
The SF6 gas dew point sensor measures the moisture content of SF6 gas. This solid-state sensor converts the measured dew point temperature to a milliamp analog signal.
Model |
Description |
OM-DPS |
Analog SF6 gas dew point temperature sensor, 5 meter cable |
OM-DPS-10 |
Analog SF6 gas dew point temperature sensor, 10 meter cable |
OM-SC5 |
5 meter cable with 90 degree connector |
Specifications
- Temperature range: -60 to 20 °C
- Mounting thread: Male 3/8" BSPP
- Seal: Neoprene O-Ring
- Accuracy: +/-2 °C
- Output signal: 4-20 milliamp DC
- Supply voltage: 10 to 32 Volts DC
- Electrical connections: 2-wire
- Operating temperature -50 to 60 °C
SF6 GAS SENSOR FILL PORT ADAPTERS
SF6 gas sensor adapters allow the range of sensors to be directly connected to a circuit breaker via the SF6 gas fill port. Integrated check valves and O-Ring seals facilitate a tight connection, mitigating the risk of a gas leak.
Model |
Description |
OM-DN8XV |
SF6 gas (2) sensor adapter, cross valve, DN8 couplings |
Model |
Description |
OM-MTV |
SF6 gas sensor adapter, tee valve, Malmquist x DN8 couplings |
Model |
Description |
OM-M2TV |
SF6 gas sensor adapter, tee valve, Malmquist couplings |
Model |
Description |
OM-DN8TV |
SF6 gas sensor adapter, tee valve, DN8 couplings |
Model |
Description |
OM-DN20TV |
SF6 gas sensor adapter, tee valve, DN20 couplings |
SF6 GAS SENSOR PIPE FITTINGS
SF6 gas sensors can be installed directly into the ¼ pipe feeding the circuit breaker's pressure gauge using SF6 gas sensor pipe fittings. All gas connections must be checked for leaks if this method is used.
Model |
Description |
OM-SAM |
SF6 gas sensor pipe fitting for (1) sensor, Mitsubishi circuit breakers only |
OM-SAM2 |
SF6 gas sensor pipe fitting for (2) sensors, Mitsubishi circuit breakers only |
OM-SAA1 |
SF6 gas sensor pipe fitting for first sensor, ABB circuit breakers only |
OM-SAA2 |
SF6 gas sensor pipe fitting for second sensor, ABB circuit breakers only |
SF6 GAS HUMIDITY ABSORBER
The SF6 gas humidity absorber is capable of passively absorbing up to 40 milliliters of water from SF6 gas, saving major expense compared to standard circuit breaker moisture removal. The corrosion-resistant absorber is easily connected to a circuit breaker's SF6 gas port.
Model |
Description |
OM-NM-DN8 |
SF6 gas humidity absorber, DN8 coupling |
OM-NM-DN20 |
SF6 gas humidity absorber, DN20 coupling |
OM-NM-MAL |
SF6 gas humidity absorber, Malmquist coupling |
Specifications
- Pre-charge: Virgin SF6 gas
- Material: Anodized aluminum and stainless steel construction
- Dimensions: 152 mm length x 10 0mm diameter (6" length x 3.94" diameter)
- Weight: 1.68 kg (3.7 lbs.)
- Absorption capacity: 40 ml (0.85 fluid ounces) of water
Voltage & Current Monitoring
Real-time voltage and current is measured with an array of high-accuracy, loop-powered voltage and current transducers. Applications include motor current, station battery voltage, heater current, and compressor run-time.
AC VOLTAGE TRANSDUCER
The AC voltage transducer is a loop-powered Voltage Transducer for measuring alternating current. It accurately converts measured AC voltage to a 4-20 milliamp signal, which can be monitored by the Optimizer3.
Model |
Description |
OM-ACVT |
AC Voltage Transducer |
Specifications
- Input voltage range: 0 - 480 VAC
- Power supply voltage: 18 - 24 volts DC
- Voltage accuracy: +/-1% of full scale
- Isolation: 2,500 volts
AC LOW-CURRENT TRANSDUCER
The AC low-current transducer is a loop-powered current transducer for measuring 50/60Hz alternating current. This transducer accurately converts measured AC current to a 4-20 milliamp signal, which can be monitored by the Optimizer3.
Model |
Description |
OM-ACLCT |
AC Low Current Transducer |
Specifications
- Selectable input current range: 0 - 2, 0 - 5 amps
- Power supply voltage: 15 - 40 volts DC
- Current accuracy:
- +/-2% of full scale in the low current range
- +/-1% of full scale in the high current range
AC CURRENT TRANSDUCER
The AC current transducer is a loop-powered, split-core current transducer for measuring 50/60Hz alternating current. This transducer accurately converts measured AC current to a 4-20 milliamp signal, which can be monitored by the Optimizer3.
Model |
Description |
OM-ACCT |
AC Current Transducer |
Specifications
- Selectable input current range: 0 - 10, 0 - 20, and 0 - 40 amps
- Power supply voltage: 12 - 30 volts DC
- Current accuracy: +/-2% from 10% to 100% of full scale
DC VOLTAGE TRANDUCER
The DC voltage transducer is a loop-powered voltage transducer which accurately converts measured DC voltage to a 4-20 milliamp signal, which can be monitored by the Optimizer3.
Model |
Description |
OM-DCVT |
DC Voltage Transducer |
Specifications
- Voltage range: 0 - 150 VDC
- Power supply voltage: 12 - 32 volts DC
- Voltage accuracy: +/-0.1% of full scale (+/-0.15 volts)
DC CURRENT TRANSDUCER
The DC current transducer is a loop-powered current transducer for measuring direct current. This transducer accurately converts measured direct current to a 4-20 milliamp signal, which can be monitored by the Optimizer3.
Model |
Description |
OM-DCCT |
DC Current Transducer |
Specifications
- Selectable current input range: 0 - 5, 0 - 10, 0 - 20 & 0 - 40 amps
- Power supply voltage: 8 - 28 volts DC
- Current accuracy: +/-0.5% of full scale
- Output circuit isolation: 1,000 volts DC
TEMPERATURE SENSOR
The temperature sensor is a loop-powered sensor which accurately converts the measured temperature to a 4-20 milliamp signal, which can be monitored by the Optimizer3.
Model |
Description |
OM-TS |
TempSense temperature sensor |
Specifications
- Power supply voltage: 12 - 30 volts DC
- Temperature accuracy: +/-2% of full scale
- Temperature range: -40 °C to 120 °C
TANK HEATER MONITORING
The Optimizer3 monitors the tank heater’s supply current using a Universal Power Status Monitor. Tank heaters are thermostatically controlled, so they do not run continuously. The power status monitor is wired in to the heater supply circuit and enables the current draw of the heaters to be monitored only when they are turned on. If one or more of the heater elements fails, the current draw will be too low and the Optimizer3 will assert a heater alarm.
UNIVERSAL POWER STATUS MONITOR
The universal power status monitor enables the Optimzer3 to monitor the AC current draw of circuit breaker tank heaters, cabinet heaters, or other high-powered electrical loads through its sensor input channels.
Model |
Description |
UPSM-241 |
Universal power status monitor with AC current transducer |
Universal Power Status Monitor Specifications
- Coil voltage: 195 - 330 VAC
- Fuse rating: 3 amps
- Dimensions: 5.1" (130 mm) L x 5.1" (130 mm) W x 4" (102 mm) H
AC Current Transducer Specifications
- Selectable input current range: 0 - 10, 0 - 20, and 0 - 40 amps
- Power supply voltage: 12 - 30 volts DC
- Current accuracy: +/-2% from 10% to 100% of full scale
TRIP CIRCUIT ISOLATION
The OM-TCI is a cost-effective method of complying with the Northeast Power Coordinating Council’s regulation requiring physical isolation of critical circuits in medium and high voltage environments. OM-TCI is used to physically isolate dual trip circuits when used in conjunction with the Optimizer Circuit Breaker Monitor (OM3D / OM3D-F).
Model |
Description |
OM-TCI |
Trip circuit isolator, includes transmitter, receiver, and a fiber optic interconnect |
OM-TCI-DIN |
Trip circuit isolator DIN Rail mounting kit |
Specifications